COP: The Coefficient
of Performance is calculated by dividing the amount of heat put out
by a heating system divided by the amount of energy put in to it. If the output
of a heat pump is 56,000 BTUH (56,000 / 3,412 = 16.4 kW), and the compressor,
fan and pumps consume 4.82 kW, the COP is:
16.4 / 4.82 = 3.4
In simple terms, you pay for
4.82 kW to operate the heat pump, and you get 16.4 kW to heat your home. That
means you get 16.4 – 4.82 = 11.58 kW from the earth. (You don’t have to pay for
those kW)
Combined COP: In a system that integrates the refrigeration with
the heating, ventilating and air conditioning (HVAC) system, it is often
possible that both the COLD and the HEAT put out by the heat pump can be
used. For example, when a system is making ice, and at the same time the heat
taken from the ice can be used to heat the building, the COP is the COLD
produced by the heat pump PLUS the HEAT produced by the heat pump divided by
the electrical input.
For example, if the
refrigeration supplied by a heat pump is 122,500 BTUH, and the heat supplied is
163,100 BTUH, the total useable output of the heat pump is:
122,500 + 163,100 = 285,600 (83.7 kW)
If the electrical input is
11.9 kW, the COP is:
83.7 / 11.9 = 7.03
Using thermal storage, such
as the “thermal storage buffer” in an ice rink, or ice storage tanks helps make
the most use of both the heating and refrigeration outputs of an integrated
system